Engineering Details for Analogue Resettable Linear Heat Sensing Cable (LHDC)
LINER HEAT SENSING CABLE Analogue/Resettable LHDCLHDC consists of insulators whose resistance varies proportionally to changes in temperature. This cable is self-restorable after the fire event as long as temperature does not exceed its specified resettable temperature limit of 120°C. Construction: overall insulated, twisted pair of tri-metallic cores Insulation: 1kV tested protective outer coat Multiple alarm temperature ratings Maximum zone length: 200 metres Compatible with any conventional or intelligent fire alarm panel Smoothing algorithms provide false alarm immunity.
Recommended Applications
Cable trays and power tunnels, Conveyor belt systems in mining & power, Floating roof crude storage tanks, Transformer bays and road tunnels
Certifications & Approvals
Certified model-wise per IS/IEC, PESO, CE, ATEX, EN, or OSHA standards.