Multi-Spectrum IR (MSIR) FL800
Description
The Model Ultra FL800 is an advanced multi-spectrum
infrared (MSIR) flame detector based on the Artificial
Intelligence Recognition Technology. The Ultra FL800 is
provided with wider field of view and further detection
range because of a multi-spectrum infrared sensor array
with a sophisticated BP Neural Network Technology
system .
The Ultra FL800 can see typical fires such as those
produced by alcohol, heptane, gasoline, jet fuels and
hydrocarbons. In addition, it can also detect and identify
non-flame signals, for example arc-welding, hot objects,
sunlight and moonlight. The Ultra FL800 is designed to
only alarm for the conditions that caused by real flame
signal, and highly immune to false alarms for non-flame
signals.
The Ultra FL800’s electronics are housed in a stainless
steel explosion-proof enclosure. The detector is available
with the following output configurations:
⇒ 4-20mA stepped output
⇒ Dual RS485 communications
⇒ HART communication
⇒ Warning, alarm and fault relays
Key Feature
⇒ Multi-Spectrum IR (MSIR) Sensor Array
⇒ BP Neural Network Technology (NNT)
⇒ Continuous Optical Path Scanning (COPS)
⇒ Redundant Communication Outputs
⇒ Event Logging
⇒ Test Mode
Specification
Model : Ultra FL800
System Specifications
Spectral Range : 2 - 5 microns (IR)
Maximum Range : 65 m
Typical Response Time : ≤ 3s (at 30m with n-Heptane fire 0.1 square meter)
≤ 5s at 65m
Maximum Field of View : 100° Horizontal, 90°Vertical
Accessories : Test lamp, mounting bracket
Classification :
ATEX:
Explosive-proof : II 2G Ex db IIC T5 Gb ( Ta = - 40°C to + 85°C )
II 2G Ex db IIC T6 Gb ( Ta = - 40°C to + 70°C )
II 2D Ex tb IIIC T100°C Db IP67
Protection Level : IP67
FM :
Explosive-proof : Class I, Division 1, GroupsB, C and D, T5,
Ta=-40°C to 85°C
Protection Level : IP67
SIL 2 Certified
Display Type : LED Displays
Warranty : Two Years
Electrical Specifications
Input Power : 20-36 VDC , 24 VDC @ 150mA (3.6W)
Analog Signal : 0-20 mA (600 ohms maximum)
3.5-20 mA (HART)
Fault Mode : <1.0mA
Test Mode : 8.0 mA , ± 0.2 mA
COPS Fault : 2 mA , ± 0.2 mA
Ready Mode : 4.0 mA , ± 0.2 mA
WARN Mode : 16 mA , ± 0.2 mA
ALARM Mode : 20 mA , ± 0.2 mA
Relay Contact Rating : 0.25 A @ 250 VAC, 2 A @ 30 VDC res.max
Baud Rate : 4800, 9600, 19200, or 38400 bit/s
HART : HART 7, HART Device Descriptor Language
available.AMSaware
Standard Configuration: Ultra FL800-1-1-1
Environmental Specifications
Operating/Storage Temperature Range :
- 40°F to + 185°F (- 40°C to + 85°C)
Operating Humidity Range :
0% to 95% RH, non-condensing
Mechanical Specifications
Housing : 316 Stainless steel
Weight : 2.5 kg
Cable Entries : Two entries 3/4 ins NPT, others optional